Skip to content

Ampacity

The table behind every gauge we recommend

A cord's ampacity is how much current it carries continuously without its insulation running too hot. For flexible cord the number comes from one table in the National Electrical Code, and the sizer on this site reads that table, nothing else.

The table

NEC Table 400.5(A)(1), copper conductors, cords rated 60 °C to 105 °C, in a 30 °C room. The resistance column is NEC Chapter 9 Table 8 and feeds the voltage-drop rule.

Gauge2 current-carrying conductors (3-wire cord)3 current-carrying conductors (4- and 5-wire)Ω per 1,000 ft (copper, 75 °C)
18 AWG10 A7 A7.770
16 AWG13 A10 A4.890
14 AWG18 A15 A3.070
12 AWG25 A20 A1.930
10 AWG30 A25 A1.210
8 AWG40 A35 A0.764
6 AWG55 A45 A0.491
4 AWG70 A60 A0.308

Which column

Count the conductors that carry current, not the conductors in the cord. A three-conductor cord — hot, neutral, ground — has two current-carrying conductors; the grounding conductor never counts. A four- or five-conductor three-phase cord has three. The second column runs lower because three heated conductors in one jacket cool each other less.

How the sizer uses it

It takes your amps and walks down the column until a gauge carries them, then checks the drop over your run. A 12 A tool on a 3-wire cord lands on 16 AWG; a 15 A saw lands on 14 AWG; 25 A on 12 AWG. Nameplate amps, not the breaker size.

What the table assumes

A cord in free air at 30 °C. Coiled on a reel under load, bundled with others, or in a hot room it carries less. If that is your case, size one gauge heavier — a config change on our side if the company adopts a derating policy, never a guess in the sizer.

The reels

The reels that carry it

Type the amps and the run; the sizer names the gauge and shows the reels in that cell by the foot and by the spool.